v2 Firmware Configuration

v2 Firmware Configuration


All drivers must be set to dp1.1.

Drivers now only require a range of DMX addresses equal to the number of channels on the unit.

Example, the DMX-SR2112 requires (12) DMX addresses, regardless of the load type(s) attached.


Accessing the Configuration Page


To access the configuration page, enter the GATEway’s IP address into any web browser, which will open the scene selection window. 

Click the menu in the top left and select “Back to Configurator”.




Creating Areas and Rooms


Areas, floors, and rooms are the organizational units for a project. Hierarchy is as follows,

AREA
 
  — FLOOR 1
       — ROOM 1
       — ROOM 2
  — FLOOR 2
       — ROOM 1
       — ROOM 2

Area – typically the project name (Smith Residence) or a specific building on a property (Pool House)

Floor – each level of the structure (First Floor, Upper Floor, etc.)

Room – a specific, separate location on a Floor (Kitchen, Dining Room, etc.)

Area(s) must be created first, followed by Floor(s) and finally Room(s).

Click  to save each entry.



Creating a Load


A Load is a single fixture or group of fixtures that will be controlled together. This is a permanent grouping, the GATEway will control any fixtures assigned to the same Load simultaneously.

Create a dedicated Floor called Enclosures with Rooms labeled Panel 1, Panel 2, etc for easier configuration later.

Refer to you Enclosure Diagrams or BOM for panel quantities.

Check the box of the Room where you’d like to create a Load, then choose the appropriate product type from the drop-down menus. Click      to save the load.

A Load can only exist in a single Room. Be sure only one Room is selected for these steps.

Refer to your Lighting Design or BOM for specific product details if needed.

Loads can be edited by hovering over the Load Name and selecting one of the tools below:

  • 🖋️ icon to edit the Load Name. 
  • ❌  icon to delete the Load.

The Load type can not be edited after a Load is created. 

If a mistake is made, simply delete the Load and recreate.

Loads can be moved between Rooms by clicking and dragging the Load Name to another Room.



Creating a Driver


Drivers are created in a similar manner as Loads and can only exist in a single Room.

If you created individual “Panel” Rooms in the previous step, create each Driver in the Panel it’s located in on the Enclosure Diagrams. Otherwise, create the Driver(s) in the appropriate Room(s).

Driver Types

DMX-SR2112

Used for 48v load types
12 channels

 

SRPC-2108-24-200CVF

Used for 24v load types
4 channels


 
SR-2108A-M5-5

Used for 24v load types
5 channels


 
SR-2108B-M24-5

Used for 24v load types
24 channels

If only (1) GATEway-1DMX exists in the project, all Drivers should be created in Universe A.

If multiple GATEway-1DMX are used, select the correct Universe of the GATEway the Driver is physically connected to.

Example,
Primary GATEway – Universe A
Secondary GATEway – Universe B
Tertiary GATEway – Universe C

Refer to your Enclosure Diagrams or BOM for the quantity of GATEway-1DMX and assigned Universes in the project.

As Drivers are created, the DMX Address will automatically index to the next available value.

The Driver type and DMX Address can not be edited after a Driver is created. 

If a mistake is made, detach any Load(s), delete the Driver, and recreate.



Connecting Loads to Drivers


Loads must be attached to a Driver(s) for proper control.

To assign Loads, navigate back to the Loads tab and select one or more Rooms from the project tree at left. Be sure to also select the Panel Room(s), if created earlier, otherwise select the Rooms where Driver(s) were created.

Expand each Driver by clicking the small arrow next to the Driver name.

Drag the Load name to the appropriate Channels on each Driver as indicated by the Enclosure Diagrams or, if no diagrams exist, where the Load has been physically attached to the Driver in the installation.

Each Load will automatically reserve the required number of Channels on the Driver based on the Load type.

Loads can only be attached to the required Driver for the Load type. Example, a 14w bulb can only be used with the DMX-SR2112 Driver.

Since a Load can include one or more fixtures, continue to connect the Load to all Drivers and Channels as needed.



Best Practices 


Finalize the gateway configuration by testing the lights directly from the GATEway before integration, assigning a static IP address to your GATEway, and creating a backup for your configuration.


Testing

It is strongly suggested the configuration is tested for correct functionality during and after setup.

Two methods of testing are available.


Testing via DMX Table
  • Available under the DMX tab
  • Allows the user to send a value to one or more DMX addresses.
  • will send a value of 255 (maximum brightness) to all 512 DMX addresses.
  • will send a value of 0 (off) to all 512 DMX addresses.
  • Alternatively, a value of 0-255 can be entered in any of the DMX addresses for control of a single fixture.



Testing via Interactive Page 

– Available under the Interactive tab
– Allows the user to control each color of a Load. Any Fixture included in the Load will be controlled.
– The top color sliders will adjust the output of the Load and the bottom most slider will control the intensity.

If a fixture does not respond during these tests, refer to the Troubleshooting section of this guide.


The GATEway-1DMX will continue to receive an IP address via DHCP after a static IP address is assigned. This is an expected behavior and cannot be disabled.


Set A Static IP Address

A static IP address can be assigned under the Tools tab.

It is strongly suggested a static IP address or MAC address reservation is created for each GATEway-1DMX. If using more than one GATEway-1DMX, all processors must have a static IP address assigned.



Create A Backup Of The Configuration

Backups of the configuration can be created at any point during setup.

Select  to create a backup and save it locally.

Creating backups periodically during configuration, after any major revisions, and once configuration is complete, is strongly suggested.



Step-By-Step Video