Wellness · Independent evaluation

Low EMF lighting, tested: what an independent engineer measured

Short answerIn August 2026 an independent electrical engineer measured one complete Colorbeam system in a home. Under those conditions it added no measurable high-frequency noise to the building supply, showed 0.25 to 0.3 mG at the face of the lights, and every tested lighting path was classified as no observable effect under IEEE 1789, from 5% to full output.

Who tested it, and how it was paid for

The evaluator was Mitch Marchand, BSc. EE., founder of EMF Aware in Calgary, Alberta, and an instructor with the Building Biology Institute. Colorbeam commissioned and funded the work. The measurements, findings and conclusions are the evaluator's.

Testing ran from August 25 to 29, 2026, with a verification retest on the last day. The paper was published in October 2026.

These are results for one system configuration under specific conditions. It was a field evaluation in a home with field-grade instruments, not an accredited laboratory test and not a product certification. Other installations can differ.

The results in one table

What was measuredResultWhere and how
AC magnetic field, BR-9W downlight0.3 mG, and 0.05 mG above 2 kHzAt the fixture
AC magnetic field, tunable white strip0.25 mG, and 0.03 mG above 2 kHzAt the fixture. About 2 in. clearance recommended
AC magnetic field, control equipmentUnder 1 mGAt 6 in., which is about the recommended clearance
High-frequency noise on the building supplyNone measurable addedEvery operating state measured, including deep dimming
Dimming frequency, strip34,826 HzConstant from 5% to full output
Dimming frequency, downlight on the SR211235,006 HzVerified configuration, after the retest
Dimming frequency, downlight on the rack pathAbout 7,056 HzBR-9W through the 4164
IEEE 1789 classNo observable effect, 3 of 3 pathsAll tested dim levels, 5% to 100%
Color rendering (CRI Ra), strip95 to 98Full output
Melanopic EDI, full output420 to 525One downlight at 3 ft, 2700K and above
Melanopic EDI, warm and dim1.5 to 5.1One downlight at 3 ft, warmest setting, 5% output

Magnetic fields at the light

The evaluator assessed the fixture results as meeting the referenced building biology guideline values, under the tested conditions and the stated clearances. Drivers and power supplies sit together, so they can go in a mechanical room or another dedicated space.

To plan for it in your own home, see low EMF lighting and the low EMF home lighting plan. For what testers look at, see building biology lighting.

Electrical noise, often called dirty electricity

Many dimming systems put high-frequency noise onto the wiring of a home, and it typically rises as lights are dimmed. In this test the changes stayed inside the normal drift of the room.

ConditionNoise on the supply
System off116 GS units
Complete system on, dimmed to 5%85 GS units
SR2112 decoder at its lowest step (1 of 255)No measurable change in noise or supply voltage

The lower reading with the system on is normal drift in the room, not a reduction caused by the system. More on the subject: dirty electricity and LED lighting.

Flicker and the stroboscopic effect

LEDs are often dimmed by switching them on and off very fast. IEEE 1789 gives 3 kHz as the frequency above which no observable effect is expected. All three paths were above it.

A second number, the stroboscopic visibility measure (SVM), shows whether motion under a light could look choppy. Below 1.0 is below the threshold of visibility for an average observer. These readings are for the SR2112 in the verified configuration.

OutputMeasured SVM
5%, the deepest light reading taken0.7 to 0.9
50%0.4 to 0.6
75%0.1 to 0.3

The deep dimming readings were taken in very low light and were attributed mainly to residual low-frequency content and sensor noise. For kitchens, gyms and other places with fast movement, the evaluator recommends scenes at 50% or higher. Flicker free lighting explains the terms.

One setting was changed, then retested

In the first session one decoder, the SR2112, was found at its 1 kHz setting. The evaluator recommended changing it. It was set to about 35 kHz and retested on August 29 across 20 points: four color temperatures at five dim levels. The retest confirmed the change and closed the finding. The results here reflect the verified configuration.

The lesson applies to any lighting system: settings matter, so ask for readings on the equipment as it will be configured in your home.

Melanopic range

Melanopic equivalent daylight illuminance (melanopic EDI) is used in lighting research to describe the spectrum and intensity of light. One downlight, measured at 3 ft, ranged from 420 to 525 at full output (2700K and above) down to 1.5 to 5.1 at its warmest setting and 5% output.

In a finished room the number depends on how many fixtures there are, where they are, the surfaces, the scene and where people sit. So treat this as the range of one fixture, not a result for a room. See melanopic light for published guidance.

How the test was done

  • Place. A home, with a blackout enclosure for the light readings. Background light was checked at 0.1 lux.
  • Distance. Downlights at 3 ft. A 6 in. sample of strip at 1 ft.
  • Points. 60 in the main light dataset, plus 20 in the retest.
  • Instruments. Fluke 289 True-RMS meter, Stetzer Microsurge Meter, EM3 three-axis meter, and In.Licht Ultra spectrometer and flicker meter.
  • System. GATEway processor, 48V power supply and SR2112 decoder, 4164 rack power supply and distribution, SRPC-2108 driver for the strip, BR-9W downlights and tunable white strip. The tested configuration had no wireless lighting components.

Use the results on your project

  1. Write the target down.Name the number you want for EMF, flicker or light.
  2. Name the configuration.List the fixtures, drivers, decoders and their settings.
  3. Plan the locations.Keep control equipment in a dedicated space, with the clearances above.
  4. Measure on site.Take readings in the finished rooms, off, full and dimmed.

The complete independent reports are available to architects, designers, integrators and building biologists on request at [email protected]. New to the subject? Start with wellness lighting or healthy home lighting.

Questions and answers

Has Colorbeam been independently tested for EMF?

Yes. Mitch Marchand, BSc. EE., of EMF Aware evaluated one complete system in a home in August 2026. Colorbeam funded the work, and the findings are the evaluator's.

What EMF level was measured at the lights?

An AC magnetic field of 0.3 mG at the BR-9W downlight and 0.25 mG at the tunable white strip, in the tested configuration.

Did the lights add dirty electricity?

No measurable high-frequency noise was added to the building supply under the tested conditions, including deep dimming.

Is this a certification?

No. It is a field evaluation of one configuration. References to IEEE, WELL, CIE and building biology are technical context and do not mean those bodies certify or endorse the system.

Will my home measure the same?

Not necessarily. Wiring, grounding, equipment settings, the rooms and the electrical surroundings all change readings. If a number matters to you, have it measured on site.

Does the test show health benefits?

No. It measured fields, electrical noise and light. It is not a medical assessment and makes no claim about health results.

Source

Have an EMF, flicker or light target?

Bring it to the call. We will talk through the configuration and what to measure.